Reference Manual
00809-0100-4530, Rev BA
July 2009
4-9
Rosemount 5300 Series
Figure 4-7. Terminal
compartment and external
ground screw.
Cable entries.
Internal Ground screw.
Terminals for signal and power supply.
Locking screw.
External Ground screw
Grounding - Foundation Fieldbus
Signal wiring of the fieldbus segment cannot be grounded. Grounding out one
of the signal wires will shut down the entire fieldbus segment.
Shield Wire Ground
To protect the fieldbus segment from noise, grounding techniques for shield
wire usually require a single grounding point for shield wire to avoid creating a
ground loop. The ground point is typically at the power supply.