Emerson Process Management ROSEMOUNT 5300 Manuel d'utilisateur Page 267

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 324
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 266
Reference Manual
00809-0100-4530, Rev BA
July 2009
C-19
Rosemount 5300 Series
To calibrate Dynamic Vapor Compensation:
1. Either choose Device Specific Configuration in the Guided Setup (if
the configuration is recommended) or Setup, Advanced.
2. Select the Vapor Compensation tab.
Figure C-16. Calibrate Dynamic
Vapor Compensation.
3. Click the Calibrate Vapor Compensation button.
4. Make sure Use Vapor Compensation is selected.
5. The echo from the reference reflector end can be viewed in the Echo
Curve in RRM. Probes shorter than 6.6 ft. (2 m) will have the reflector
end at 0.75 ft. (0.23 m) distance and probes longer than 6.6 ft. (2 m) will
have the reflector end at 1.6 ft. (0.5 m).
6. Cycle power to finish.
In 375 Field Communicator, the calibration can be done by HART command
[2, 7, 3].
Vue de la page 266
1 2 ... 262 263 264 265 266 267 268 269 270 271 272 ... 323 324

Commentaires sur ces manuels

Pas de commentaire