Emerson Process Management ROSEMOUNT 5300 Manuel d'utilisateur

Naviguer en ligne ou télécharger Manuel d'utilisateur pour Mesure, test et contrôle Emerson Process Management ROSEMOUNT 5300. Emerson Process Management ROSEMOUNT 5300 User's Manual Manuel d'utilisatio

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer

Résumé du contenu

Page 1 - Rosemount 5300 Series

www.rosemount.comReference Manual 00809-0100-4530, Rev BAJuly 2009Rosemount 5300 SeriesSuperior Performance Guided Wave Radar

Page 2

Reference Manual00809-0100-4530, Rev BAJuly 2009Rosemount 5300 SeriesTOC-6APPENDIX GRegister Transducer BlockOverview . . . . . . . . . . . . . . . .

Page 3 - Interface Transmitters

Reference Manual00809-0100-4530, Rev BAJuly 2009Rosemount 5300 Series5-28Restart the Transmitter13. Restart the transmitterWhen the transmitter is con

Page 4

Reference Manual 00809-0100-4530, Rev BAJuly 20095-29Rosemount 5300 SeriesThis information may be useful for:• installing another 5300 in a similar ta

Page 5 - Table of Contents

Reference Manual00809-0100-4530, Rev BAJuly 2009Rosemount 5300 Series5-30BASIC CONFIGURATION USING AMS SUITE (HART)The Rosemount 5300 transmitter can

Page 6

Reference Manual 00809-0100-4530, Rev BAJuly 20095-31Rosemount 5300 SeriesBASIC CONFIGURATION USING DELTAVThe Rosemount 5300 Series supports DD Method

Page 7

Reference Manual00809-0100-4530, Rev BAJuly 2009Rosemount 5300 Series5-326. Select the TRANSDUCER1100 block and choose the Probe tab.FOUNDATION Fieldb

Page 8

Reference Manual 00809-0100-4530, Rev BAJuly 20095-33Rosemount 5300 Series7. Select the TRANSDUCER1100 block and choose the Geometry tab.8. Tank Heigh

Page 9

Reference Manual00809-0100-4530, Rev BAJuly 2009Rosemount 5300 Series5-34Submerged is used for applications where the probe is fully submerged in liqu

Page 10

Reference Manual 00809-0100-4530, Rev BAJuly 20095-35Rosemount 5300 Series15. Choose a pre-defined calculation method based on a tank shape that corre

Page 11 - Section 1 Introduction

Reference Manual00809-0100-4530, Rev BAJuly 2009Rosemount 5300 Series5-36FOUNDATION FIELDBUS OVERVIEWFigure 5-10 illustrates how the signals are chann

Page 12

Reference Manual 00809-0100-4530, Rev BAJuly 20095-37Rosemount 5300 SeriesFOUNDATION Fieldbus Block OperationFunction blocks within the fieldbus devic

Page 13

Reference Manual 00809-0100-4530, Rev BAJuly 2009Rosemount 5300 Serieswww.rosemount.comSection 1 IntroductionSafety Messages . . . . . . . . . . . . .

Page 14

Reference Manual00809-0100-4530, Rev BAJuly 2009Rosemount 5300 Series5-38Analog Input BlockFigure 5-11. Analog-Input BlockThe Analog Input (AI) functi

Page 15

Reference Manual 00809-0100-4530, Rev BAJuly 20095-39Rosemount 5300 SeriesCONFIGURE THE AI BLOCKA minimum of four parameters are required to configure

Page 16

Reference Manual00809-0100-4530, Rev BAJuly 2009Rosemount 5300 Series5-40Indirect Square RootSelect indirect square root when the desired output is an

Page 17

Reference Manual 00809-0100-4530, Rev BAJuly 20095-41Rosemount 5300 SeriesEngineering UnitsNOTE!To avoid configuration errors, only select Engineering

Page 18

Reference Manual00809-0100-4530, Rev BAJuly 2009Rosemount 5300 Series5-42Application Example 1 Radar Level Transmitter, Level ValueA level transmitter

Page 19

Reference Manual 00809-0100-4530, Rev BAJuly 20095-43Rosemount 5300 SeriesApplication Example 2 Radar Level Gauge, Level value in percent (%)The maxim

Page 20

Reference Manual00809-0100-4530, Rev BAJuly 2009Rosemount 5300 Series5-44Application Example 3 Radar Level Transmitter, Product Level and Interface Le

Page 21

Reference Manual 00809-0100-4530, Rev BAJuly 20095-45Rosemount 5300 SeriesTRI-LOOP HART TO ANALOG CONVERTERThe Rosemount 333 HART Tri-Loop HART-to-Ana

Page 22

Reference Manual00809-0100-4530, Rev BAJuly 2009Rosemount 5300 Series5-467. Configure Tri-Loop Channel 1:a. Assign variable: Tri-Loop HART command [1,

Page 23

Reference Manual 00809-0100-4530, Rev BAJuly 20095-47Rosemount 5300 SeriesHART MULTI-DROP CONFIGURATIONThe 5300 transmitter can be run in multidrop mo

Page 24

Reference Manual00809-0100-4530, Rev BAJuly 2009Rosemount 5300 Series1-2MANUAL OVERVIEW This manual provides installation, configuration and maintenan

Page 25

Reference Manual00809-0100-4530, Rev BAJuly 2009Rosemount 5300 Series5-48

Page 26

Reference Manual 00809-0100-4530, Rev BAJuly 2009Rosemount 5300 Serieswww.rosemount.comSection 6 OperationSafety Messages . . . . . . . . . . . . . .

Page 27

Reference Manual00809-0100-4530, Rev BAJuly 2009Rosemount 5300 Series6-2VIEWING MEASUREMENT DATAUsing the Display Panel The Rosemount 5300 transmitter

Page 28

Reference Manual 00809-0100-4530, Rev BAJuly 20096-3Rosemount 5300 SeriesSpecifying Display Panel VariablesIt is possible to specify the variables to

Page 29

Reference Manual00809-0100-4530, Rev BAJuly 2009Rosemount 5300 Series6-4Using AMSThe LCD tab in the Configure/Setup window lets you specify which vari

Page 30

Reference Manual 00809-0100-4530, Rev BAJuly 20096-5Rosemount 5300 SeriesUsing DeltaV1. Click the right mouse button on the transmitter icon and choos

Page 31

Reference Manual00809-0100-4530, Rev BAJuly 2009Rosemount 5300 Series6-6LCD ParametersTable 6-1. LCD parameters and presentation on displayParameter

Page 32

Reference Manual 00809-0100-4530, Rev BAJuly 20096-7Rosemount 5300 SeriesViewing Measurement Data in RRMTo view measurement data such as Level, Signal

Page 33

Reference Manual00809-0100-4530, Rev BAJuly 2009Rosemount 5300 Series6-8Viewing Measurement Data in AMS SuiteTo view measurement data such as Level, S

Page 34

Reference Manual 00809-0100-4530, Rev BAJuly 20096-9Rosemount 5300 SeriesViewing Measurement Data in DeltaV1. Click the right mouse button on the tran

Page 35

Reference Manual 00809-0100-4530, Rev BAJuly 20091-3Rosemount 5300 SeriesAppendix B: Product Certifications• Labels• European ATEX Directive informati

Page 36

Reference Manual00809-0100-4530, Rev BAJuly 2009Rosemount 5300 Series6-10

Page 37

Reference Manual 00809-0100-4530, Rev BAJuly 2009Rosemount 5300 Serieswww.rosemount.comSection 7 Service and TroubleshootingSafety messages . . . . .

Page 38

Reference Manual00809-0100-4530, Rev BAJuly 2009Rosemount 5300 Series7-2.Explosions could result in death or serious injury.Verify that the operating

Page 39

Reference Manual 00809-0100-4530, Rev BAJuly 20097-3Rosemount 5300 SeriesANALYZING THE MEASUREMENT SIGNALRosemount Radar Master (RRM) and other tools

Page 40

Reference Manual00809-0100-4530, Rev BAJuly 2009Rosemount 5300 Series7-4Surface Threshold - amplitude threshold for detection of the Product level pea

Page 41

Reference Manual 00809-0100-4530, Rev BAJuly 20097-5Rosemount 5300 SeriesSURFACE PULSE NOT FOUNDThe amplitude thresholds are automatically adjusted to

Page 42

Reference Manual00809-0100-4530, Rev BAJuly 2009Rosemount 5300 Series7-6Figure 7-3. Example 2: surface threshold is too low.By adjusting the surface t

Page 43

Reference Manual 00809-0100-4530, Rev BAJuly 20097-7Rosemount 5300 SeriesDISTURBANCE ECHO HANDLINGWhen the Basic Configuration is done, the transmitte

Page 44

Reference Manual00809-0100-4530, Rev BAJuly 2009Rosemount 5300 Series7-8INTERFACE PULSE NOT FOUNDIn interface applications where the bottom product ha

Page 45

Reference Manual 00809-0100-4530, Rev BAJuly 20097-9Rosemount 5300 SeriesFigure 7-7. After changing the amplitude threshold the transmitter detects th

Page 46

Reference Manual00809-0100-4530, Rev BAJuly 2009Rosemount 5300 Series1-4The center will ask for product model and serial numbers, and will provide a R

Page 47

Reference Manual00809-0100-4530, Rev BAJuly 2009Rosemount 5300 Series7-10USING THE ECHO CURVE ANALYZERThe Echo Curve Analyzer in Rosemount Radar Maste

Page 48

Reference Manual 00809-0100-4530, Rev BAJuly 20097-11Rosemount 5300 SeriesThe Configuration Mode TabThe Configuration Mode tab lets you adjust the dif

Page 49

Reference Manual00809-0100-4530, Rev BAJuly 2009Rosemount 5300 Series7-12The current level Measurement Output from the device is presented with an arr

Page 50

Reference Manual 00809-0100-4530, Rev BAJuly 20097-13Rosemount 5300 SeriesRecord Tank SpectraThis function allows you to record tank spectra over time

Page 51

Reference Manual00809-0100-4530, Rev BAJuly 2009Rosemount 5300 Series7-141. Select HART command [2, 5, 2].FOUNDATION Fieldbus parameter:TRANSDUCER 130

Page 52

Reference Manual 00809-0100-4530, Rev BAJuly 20097-15Rosemount 5300 SeriesINTERFACE MEASUREMENTS WITH FULLY SUBMERGED PROBESThe Rosemount 5300 series

Page 53

Reference Manual00809-0100-4530, Rev BAJuly 2009Rosemount 5300 Series7-16ANALOG OUTPUT CALIBRATIONThis function lets you calibrate the Analog Output b

Page 54

Reference Manual 00809-0100-4530, Rev BAJuly 20097-17Rosemount 5300 SeriesLEVEL AND DISTANCE CALIBRATIONLevel and distance calibration may be necessar

Page 55

Reference Manual00809-0100-4530, Rev BAJuly 2009Rosemount 5300 Series7-18Figure 7-12. Distance and Level calibrationLevelReference PointReference Gaug

Page 56

Reference Manual 00809-0100-4530, Rev BAJuly 20097-19Rosemount 5300 SeriesLOGGING MEASUREMENT DATA By using the Log Device Registers function in the R

Page 57

Reference Manual 00809-0100-4530, Rev BAJuly 2009Rosemount 5300 Serieswww.rosemount.comSection 2 Transmitter OverviewTheory of Operation . . . . . .

Page 58

Reference Manual00809-0100-4530, Rev BAJuly 2009Rosemount 5300 Series7-20BACKING UP THE TRANSMITTER CONFIGURATIONUse this RRM option to make a backup

Page 59

Reference Manual 00809-0100-4530, Rev BAJuly 20097-21Rosemount 5300 SeriesCONFIGURATION REPORTThis function in RRM shows what configuration changes ha

Page 60

Reference Manual00809-0100-4530, Rev BAJuly 2009Rosemount 5300 Series7-22RESET TO FACTORY SETTINGSThis function resets all or a specific part of the h

Page 61

Reference Manual 00809-0100-4530, Rev BAJuly 20097-23Rosemount 5300 SeriesDIAGNOSTICS The following information about the device can be retrieved:• de

Page 62

Reference Manual00809-0100-4530, Rev BAJuly 2009Rosemount 5300 Series7-24DeltaV1. In the DeltaV Explorer, select the desired transmitter icon, and cli

Page 63

Reference Manual 00809-0100-4530, Rev BAJuly 20097-25Rosemount 5300 SeriesUSING THE SIMULATION MODEThis function can be used to simulate measurements

Page 64

Reference Manual00809-0100-4530, Rev BAJuly 2009Rosemount 5300 Series7-26WRITE PROTECTING A TRANSMITTERA Rosemount 5300 Series transmitter can be prot

Page 65

Reference Manual 00809-0100-4530, Rev BAJuly 20097-27Rosemount 5300 SeriesVIEWING INPUT AND HOLDING REGISTERSMeasured data is continuously stored in t

Page 66

Reference Manual00809-0100-4530, Rev BAJuly 2009Rosemount 5300 Series7-28REMOVING THE TRANSMITTER HEAD1. Loosen the nut that connects the transmitter

Page 67

Reference Manual 00809-0100-4530, Rev BAJuly 20097-29Rosemount 5300 SeriesCHANGING A PROBEProbe and Firmware CompatibilityTransmitter heads with a fir

Page 68

Reference Manual00809-0100-4530, Rev BAJuly 2009Rosemount 5300 Series2-2APPLICATIONS The Rosemount 5300 Series Radar Transmitter series is suited for

Page 69

Reference Manual00809-0100-4530, Rev BAJuly 2009Rosemount 5300 Series7-30Check Firmware and Probe Version1. Check the manufacturing date on the transm

Page 70

Reference Manual 00809-0100-4530, Rev BAJuly 20097-31Rosemount 5300 SeriesChanging the Probe1. Loosen the nut.2. Remove the transmitter head from the

Page 71

Reference Manual00809-0100-4530, Rev BAJuly 2009Rosemount 5300 Series7-32Figure 7-23. Product level lowered beneath the Near Zone.Table 7-2. Near Zon

Page 72

Reference Manual 00809-0100-4530, Rev BAJuly 20097-33Rosemount 5300 SeriesDIAGNOSTIC MESSAGESTroubleshooting If there is a malfunction despite the abs

Page 73 - Section 5 Configuration

Reference Manual00809-0100-4530, Rev BAJuly 2009Rosemount 5300 Series7-34The reference pulse is not detected.• The tank is full• The transmitter is co

Page 74

Reference Manual 00809-0100-4530, Rev BAJuly 20097-35Rosemount 5300 SeriesDevice Status Device Status messages that may appear on the Integral Display

Page 75

Reference Manual00809-0100-4530, Rev BAJuly 2009Rosemount 5300 Series7-36Errors Error messages that may be displayed on the Integral Display, on a 375

Page 76

Reference Manual 00809-0100-4530, Rev BAJuly 20097-37Rosemount 5300 SeriesWarnings Table 7-6 shows a list of diagnostic messages that may be displayed

Page 77

Reference Manual00809-0100-4530, Rev BAJuly 2009Rosemount 5300 Series7-38Measurement Status Measurement Status messages that may appear on the Integra

Page 78

Reference Manual 00809-0100-4530, Rev BAJuly 20097-39Rosemount 5300 SeriesSim mode 0 active The simulation mode is active. The given measurements are

Page 79

Reference Manual 00809-0100-4530, Rev BAJuly 20092-3Rosemount 5300 SeriesThe Rosemount 5302 measures both level and interface level in a separator tan

Page 80

Reference Manual00809-0100-4530, Rev BAJuly 2009Rosemount 5300 Series7-40Interface Status Interface Status messages that may appear on the Integral Di

Page 81

Reference Manual 00809-0100-4530, Rev BAJuly 20097-41Rosemount 5300 SeriesAnalog Output Status Analog Output Status messages that may appear on the In

Page 82

Reference Manual00809-0100-4530, Rev BAJuly 2009Rosemount 5300 Series7-42LCD ERROR MESSAGESFigure 7-24. The 5300 Display Panel displaying an error mes

Page 83

Reference Manual 00809-0100-4530, Rev BAJuly 20097-43Rosemount 5300 SeriesLED ERROR MESSAGES For Rosemount 5300 transmitters without display, a flashi

Page 84

Reference Manual00809-0100-4530, Rev BAJuly 2009Rosemount 5300 Series7-44FOUNDATION FIELDBUS ERROR MESSAGESResource Block This section describes error

Page 85

Reference Manual 00809-0100-4530, Rev BAJuly 20097-45Rosemount 5300 SeriesTransducer Block This section describes error conditions found in the Sensor

Page 86

Reference Manual00809-0100-4530, Rev BAJuly 2009Rosemount 5300 Series7-46Table 7-19. Troubleshooting the AI blockSymptom Possible Causes Recommended

Page 87

Reference Manual 00809-0100-4530, Rev BAJuly 2009Rosemount 5300 Serieswww.rosemount.comSection 8 Safety Instrumented Systems (4-20 mA only)Safety Mess

Page 88

Reference Manual00809-0100-4530, Rev BAJuly 2009Rosemount 5300 Series8-2Any substitution of non-authorized parts or repair, other than exchanging the

Page 89

Reference Manual 00809-0100-4530, Rev BAJuly 20098-3Rosemount 5300 SeriesOVERVIEW The following section applies to the 4-20 mA Rosemount 5300 Prior-Us

Page 90

Reference Manual00809-0100-4530, Rev BAJuly 2009Rosemount 5300 Series2-4Model 5303, with a flexible single lead probe, is the solution for solids, pow

Page 91

Reference Manual00809-0100-4530, Rev BAJuly 2009Rosemount 5300 Series8-4NOTE!The Rosemount 5300 transmitter is not safety-rated during maintenance wor

Page 92

Reference Manual 00809-0100-4530, Rev BAJuly 20098-5Rosemount 5300 SeriesAlarm and Saturation LevelsDCS or safety logic solver should be configured to

Page 93

Reference Manual00809-0100-4530, Rev BAJuly 2009Rosemount 5300 Series8-6If the overfill and empty tank protection function cannot be tested by a contr

Page 94

Reference Manual 00809-0100-4530, Rev BAJuly 20098-7Rosemount 5300 SeriesInspection Visual InspectionIt is recommended to inspect the probe for possib

Page 95

Reference Manual00809-0100-4530, Rev BAJuly 2009Rosemount 5300 Series8-8

Page 96

Reference Manual 00809-0100-4530, Rev BAJuly 2009Rosemount 5300 Serieswww.rosemount.comAppendix A Reference DataSpecifications . . . . . . . . . . .

Page 97

Reference Manual00809-0100-4530, Rev BAJuly 2009Rosemount 5300 SeriesA-2Display / Configuration (continued)FOUNDATION Fieldbus Class (Basic or Link Ma

Page 98

Reference Manual 00809-0100-4530, Rev BAJuly 2009A-3Rosemount 5300 SeriesMechanical (continued)Dimensions See “Dimensional Drawings” on page A-9.Probe

Page 99

Reference Manual00809-0100-4530, Rev BAJuly 2009Rosemount 5300 SeriesA-4Process Temperature and Pressure RatingThe tank connection consists of a tank

Page 100

Reference Manual 00809-0100-4530, Rev BAJuly 2009A-5Rosemount 5300 SeriesFigure A-2. Maximum process temperature and pressure diagram for HTHP tank co

Page 101

Reference Manual 00809-0100-4530, Rev BAJuly 20092-5Rosemount 5300 SeriesCOMPONENTS OF THE TRANSMITTERThe Rosemount 5300 Series Radar Transmitter has

Page 102

Reference Manual00809-0100-4530, Rev BAJuly 2009Rosemount 5300 SeriesA-6Table A-1. Temperature range for different tank seal material.For Tri-Clamps,

Page 103

Reference Manual 00809-0100-4530, Rev BAJuly 2009A-7Rosemount 5300 Series• EN:316L SST according to EN 1092-1 Table 18, material group 13E0.Standard:

Page 104

Reference Manual00809-0100-4530, Rev BAJuly 2009Rosemount 5300 SeriesA-8Remote Housing Measuring RangeThis table shows the maximum recommended measuri

Page 105

Reference Manual 00809-0100-4530, Rev BAJuly 2009A-9Rosemount 5300 SeriesDIMENSIONAL DRAWINGSProbe Type 4A, 4BFigure A-6. Rigid Single Lead Probe with

Page 106

Reference Manual00809-0100-4530, Rev BAJuly 2009Rosemount 5300 SeriesA-10Figure A-7. Rigid Single Lead Probe with Tri-Clamp ConnectionDimensions are i

Page 107

Reference Manual 00809-0100-4530, Rev BAJuly 2009A-11Rosemount 5300 SeriesFigure A-8. Rigid Single Lead with threaded connectionDimensions are in inch

Page 108

Reference Manual00809-0100-4530, Rev BAJuly 2009Rosemount 5300 SeriesA-12Figure A-9. Flexible Single Lead Probe with Flange ConnectionProbe Type 5A, 5

Page 109

Reference Manual 00809-0100-4530, Rev BAJuly 2009A-13Rosemount 5300 SeriesFigure A-10. Flexible Single Lead Probe with Tri-Clamp ConnectionDimensions

Page 110

Reference Manual00809-0100-4530, Rev BAJuly 2009Rosemount 5300 SeriesA-14Figure A-11. Flexible Single Lead with threaded connectionDimensions are in i

Page 111

Reference Manual 00809-0100-4530, Rev BAJuly 2009A-15Rosemount 5300 SeriesFigure A-12. Coaxial probe with flange connectionProbe Type 3A, 3BDimensions

Page 113

Reference Manual00809-0100-4530, Rev BAJuly 2009Rosemount 5300 Series2-6Figure 2-4. Remote Housing components.Remote Housing allows for the transmitte

Page 114

Reference Manual00809-0100-4530, Rev BAJuly 2009Rosemount 5300 SeriesA-16Figure A-13. Coaxial probe with threaded connectionDimensions are in inches (

Page 115

Reference Manual 00809-0100-4530, Rev BAJuly 2009A-17Rosemount 5300 SeriesFigure A-14. Rigid Twin Lead Probe Type 1ADimensions are in inches (millime

Page 116

Reference Manual00809-0100-4530, Rev BAJuly 2009Rosemount 5300 SeriesA-18Figure A-15. Flexible Twin Lead Probe Type 2ADimensions are in inches (millim

Page 117

Reference Manual 00809-0100-4530, Rev BAJuly 2009A-19Rosemount 5300 SeriesFigure A-16. Bracket mounting.Dimensions are in inches (millimeters). Pipe d

Page 118

Reference Manual00809-0100-4530, Rev BAJuly 2009Rosemount 5300 SeriesA-20Figure A-17. Remote housing.Dimensions are in inches (millimeters).5.2 (133)5

Page 119

Reference Manual 00809-0100-4530, Rev BAJuly 2009A-21Rosemount 5300 SeriesORDERING INFORMATIONModel Code 5301 and 5302 Level and/or Interface in Liqui

Page 120

Reference Manual00809-0100-4530, Rev BAJuly 2009Rosemount 5300 SeriesA-22Code Probe Type Process Connection Probe Lengths1A Rigid Twin Lead(9)Flange /

Page 121 - Section 6 Operation

Reference Manual 00809-0100-4530, Rev BAJuly 2009A-23Rosemount 5300 SeriesEN (DIN) Flanges(15)HB DN50, PN40HC DN50, PN63. HTHP / HP unitsHD DN50, PN10

Page 122

Reference Manual00809-0100-4530, Rev BAJuly 2009Rosemount 5300 SeriesA-24Code Hazardous Locations CertificationsNA No Hazardous Locations Certificatio

Page 123

Reference Manual 00809-0100-4530, Rev BAJuly 2009A-25Rosemount 5300 SeriesPlantWeb Diagnostic FunctionalityD01 FOUNDATION fieldbus Diagnostics SuiteDA

Page 124

Reference Manual 00809-0100-4530, Rev BAJuly 20092-7Rosemount 5300 SeriesSYSTEM ARCHITECTUREThe Rosemount 5300 Series Radar Transmitter is loop-powere

Page 125

Reference Manual00809-0100-4530, Rev BAJuly 2009Rosemount 5300 SeriesA-26Model Code 5303, Level for Solids Model Product Description5303 Guided Wave S

Page 126

Reference Manual 00809-0100-4530, Rev BAJuly 2009A-27Rosemount 5300 SeriesCode Process Connection - Size / Type (consult the factory for other process

Page 127

Reference Manual00809-0100-4530, Rev BAJuly 2009Rosemount 5300 SeriesA-28Code Hazardous Locations CertificationsNA No Hazardous Locations Certificatio

Page 128

Reference Manual 00809-0100-4530, Rev BAJuly 2009A-29Rosemount 5300 SeriesPlantWeb Diagnostic FunctionalityD01 FOUNDATION fieldbus Diagnostics SuiteDA

Page 129

Reference Manual00809-0100-4530, Rev BAJuly 2009Rosemount 5300 SeriesA-30SPARE PARTSSpare parts list Transmitter head Model 5301/5302/5303Model Produc

Page 130

Reference Manual 00809-0100-4530, Rev BAJuly 2009A-31Rosemount 5300 SeriesCode Hazardous Locations Certifications (continued)IF CSA FISCO Intrinsic Sa

Page 131

Reference Manual00809-0100-4530, Rev BAJuly 2009Rosemount 5300 SeriesA-32Spare parts list Probe Model 5301/5302/5303Model Product Description5309 Spar

Page 132

Reference Manual 00809-0100-4530, Rev BAJuly 2009A-33Rosemount 5300 SeriesCode Probe Type Process Connection Probe Lengths4V Vapor Single Rigid Probe

Page 133

Reference Manual00809-0100-4530, Rev BAJuly 2009Rosemount 5300 SeriesA-34EN (DIN) Flanges(14) (continued)ID DN80, PN100. HTHP / HP unitsIE DN80, PN160

Page 134

Reference Manual 00809-0100-4530, Rev BAJuly 2009A-35Rosemount 5300 SeriesCode Options (continued)W2 Short weight for flexible single lead probe(19)BR

Page 135

Reference Manual00809-0100-4530, Rev BAJuly 2009Rosemount 5300 Series2-8Figure 2-6. FOUNDATION Fieldbus system architecture Host/DCS system (e.g. Delt

Page 136

Reference Manual00809-0100-4530, Rev BAJuly 2009Rosemount 5300 SeriesA-36Spare parts list Other Spares and Accessories Rosemount 5300 SeriesCode Proce

Page 137

Reference Manual 00809-0100-4530, Rev BAJuly 2009A-37Rosemount 5300 Series(1) If a centering disc is required for a flanged probe the centering disc c

Page 138

Reference Manual00809-0100-4530, Rev BAJuly 2009Rosemount 5300 SeriesA-38

Page 139

Reference Manual 00809-0100-4530, Rev BAJuly 2009Rosemount 5300 Serieswww.rosemount.comAppendix B Product CertificationsSafety messages . . . . . . .

Page 140

Reference Manual00809-0100-4530, Rev BAJuly 2009Rosemount 5300 SeriesB-2EU CONFORMITY The EC declaration of conformity for all applicable European dir

Page 141

Reference Manual 00809-0100-4530, Rev BAJuly 2009B-3Rosemount 5300 SeriesEUROPEAN ATEX DIRECTIVE INFORMATIONIntrinsic Safety The Rosemount 5300 Series

Page 142

Reference Manual00809-0100-4530, Rev BAJuly 2009Rosemount 5300 SeriesB-4Figure B-2. Approval Label ATEX Foundation Fieldbus modelI1 The following info

Page 143

Reference Manual 00809-0100-4530, Rev BAJuly 2009B-5Rosemount 5300 SeriesFigure B-3. Approval Label ATEX FISCO modelIA The following information is pr

Page 144

Reference Manual00809-0100-4530, Rev BAJuly 2009Rosemount 5300 SeriesB-6Flameproof The Rosemount 5300 Series Guided Wave Radar Level Transmitter that

Page 145

Reference Manual 00809-0100-4530, Rev BAJuly 2009B-7Rosemount 5300 SeriesFigure B-5. Approval Label ATEX Foundation Fieldbus E1 The following informa

Page 146

Reference Manual 00809-0100-4530, Rev BAJuly 20092-9Rosemount 5300 SeriesPROBE SELECTION GUIDEThe following guidelines should be used to choose the ap

Page 147

Reference Manual00809-0100-4530, Rev BAJuly 2009Rosemount 5300 SeriesB-8NATIONAL SUPERVISION AND INSPECTION CENTER FOR EXPLOSION PROTECTION AND SAFETY

Page 148

Reference Manual 00809-0100-4530, Rev BAJuly 2009B-9Rosemount 5300 SeriesFigure B-7. Approval LabelNational Supervision and Inspection Center for Expl

Page 149

Reference Manual00809-0100-4530, Rev BAJuly 2009Rosemount 5300 SeriesB-10Figure B-8. Approval LabelNational Supervision and Inspection Center for Expl

Page 150

Reference Manual 00809-0100-4530, Rev BAJuly 2009B-11Rosemount 5300 SeriesFACTORY MUTUAL (FM) APPROVALSThe Rosemount 5300 Series Guided Wave Radar Lev

Page 151

Reference Manual00809-0100-4530, Rev BAJuly 2009Rosemount 5300 SeriesB-12Figure B-10. Approval Labels Factory Mutual (FM) Foundation Fieldbus modelI5

Page 152

Reference Manual 00809-0100-4530, Rev BAJuly 2009B-13Rosemount 5300 SeriesExplosion ProofFigure B-12. Approval Labels Factory Mutual (FM) HART modelE5

Page 153

Reference Manual00809-0100-4530, Rev BAJuly 2009Rosemount 5300 SeriesB-14CANADIAN STANDARDS ASSOCIATION (CSA) APPROVALThis product meets the Dual Seal

Page 154

Reference Manual 00809-0100-4530, Rev BAJuly 2009B-15Rosemount 5300 SeriesFigure B-15. Approval Label Canadian Standards Association (CSA) Foundation

Page 155

Reference Manual00809-0100-4530, Rev BAJuly 2009Rosemount 5300 SeriesB-16Explosion Proof Cert. no. 1514653.Figure B-17. Approval Label Canadian Standa

Page 156

Reference Manual 00809-0100-4530, Rev BAJuly 2009B-17Rosemount 5300 SeriesIECEX APPROVALIntrinsic SafetyFigure B-19. Approval Label IECEx HART modelI7

Page 157

Reference Manual00809-0100-4530, Rev BAJuly 2009Rosemount 5300 Series2-10Transition Zones The measuring range depends on probe type and product proper

Page 158

Reference Manual00809-0100-4530, Rev BAJuly 2009Rosemount 5300 SeriesB-18Figure B-20. Approval Label IECEx Foundation Fieldbus modelI7 Intrinsically S

Page 159

Reference Manual 00809-0100-4530, Rev BAJuly 2009B-19Rosemount 5300 SeriesFigure B-21. Approval Label IECEx FISCO modelIG Intrinsically SafeEx ia IIC

Page 160

Reference Manual00809-0100-4530, Rev BAJuly 2009Rosemount 5300 SeriesB-20FlameproofFigure B-22. Approval Labels IECEx HARTE7 FlameproofEx iad IIC T4 (

Page 161

Reference Manual 00809-0100-4530, Rev BAJuly 2009B-21Rosemount 5300 SeriesFigure B-23. Approval Labels IECEx Foundation FieldbusE7 FlameproofEx iad II

Page 162

Reference Manual00809-0100-4530, Rev BAJuly 2009Rosemount 5300 SeriesB-22COMBINATION APPROVALSKA ATEX, FM, CSA Flameproof/Explosion-proofKB ATEX, FM,

Page 163

Reference Manual 00809-0100-4530, Rev BAJuly 2009B-23Rosemount 5300 SeriesFigure B-24. System Control Drawing for hazardous location installation of i

Page 164

Reference Manual00809-0100-4530, Rev BAJuly 2009Rosemount 5300 SeriesB-24Figure B-25. Installation Drawing for hazardous location installation of intr

Page 165

Reference Manual 00809-0100-4530, Rev BAJuly 2009B-25Rosemount 5300 SeriesFigure B-26. Installation Drawing for hazardous location installation of int

Page 166

Reference Manual00809-0100-4530, Rev BAJuly 2009Rosemount 5300 SeriesB-26

Page 167

Reference Manual 00809-0100-4530, Rev BAJuly 2009Rosemount 5300 Serieswww.rosemount.comAppendix C Advanced ConfigurationSafety messages . . . . . . .

Page 168

Reference Manual 00809-0100-4530, Rev BAJuly 20092-11Rosemount 5300 SeriesPROCESS CHARACTERISTICSThe Rosemount 5300 Series has high sensitivity becaus

Page 169

Reference Manual00809-0100-4530, Rev BAJuly 2009Rosemount 5300 SeriesC-2Failure to follow safe installation and servicing guidelines could result in d

Page 170

Reference Manual 00809-0100-4530, Rev BAJuly 2009C-3Rosemount 5300 SeriesUSER DEFINED UPPER REFERENCE POINTAn Upper Reference Point other than the sta

Page 171

Reference Manual00809-0100-4530, Rev BAJuly 2009Rosemount 5300 SeriesC-4HANDLING OF DISTURBANCES FROM NOZZLETrim Near Zone Using the Trim Near Zone Fu

Page 172

Reference Manual 00809-0100-4530, Rev BAJuly 2009C-5Rosemount 5300 SeriesNOTE!Note that for firmware version 2.A2 the Trim Near Zone is not possible i

Page 173

Reference Manual00809-0100-4530, Rev BAJuly 2009Rosemount 5300 SeriesC-6NOTE!The Trim Near Zone function can be reset by selecting Reset near zone tri

Page 174

Reference Manual 00809-0100-4530, Rev BAJuly 2009C-7Rosemount 5300 SeriesChanging the Upper Null ZoneMeasurements are not performed within the Upper N

Page 175

Reference Manual00809-0100-4530, Rev BAJuly 2009Rosemount 5300 SeriesC-8THRESHOLD SETTINGS Measurement with the Rosemount 5300 is based on the fact th

Page 176

Reference Manual 00809-0100-4530, Rev BAJuly 2009C-9Rosemount 5300 SeriesReference ThresholdAmplitude threshold for detection of the Reference pulse.P

Page 177

Reference Manual00809-0100-4530, Rev BAJuly 2009Rosemount 5300 SeriesC-10PROBE END PROJECTIONProbe End Projection allows you to measure product level

Page 178

Reference Manual 00809-0100-4530, Rev BAJuly 2009C-11Rosemount 5300 SeriesProbe End Projection is used to :• Use the probe end echo as reference, in c

Page 179

Reference Manual00809-0100-4530, Rev BAJuly 2009Rosemount 5300 Series2-12Measuring Range The measuring range differs depending on probe type and chara

Page 180

Reference Manual00809-0100-4530, Rev BAJuly 2009Rosemount 5300 SeriesC-12Reset DC Estimation: Resets DC estimation to the configured initial value, fo

Page 181

Reference Manual 00809-0100-4530, Rev BAJuly 2009C-13Rosemount 5300 SeriesUse Automatic Echo Tracking SettingsWhen this check-box is selected, the tra

Page 182

Reference Manual00809-0100-4530, Rev BAJuly 2009Rosemount 5300 SeriesC-14DIELECTRIC CONSTANT SETTINGSStatic Vapor CompensationIn some applications, th

Page 183

Reference Manual 00809-0100-4530, Rev BAJuly 2009C-15Rosemount 5300 SeriesDYNAMIC VAPOR COMPENSATIONRosemount 5300 Series is based on the Time Domain

Page 184

Reference Manual00809-0100-4530, Rev BAJuly 2009Rosemount 5300 SeriesC-16The Rosemount 5300 uses a reference reflector mounted on the probe at a certa

Page 185 - Appendix A Reference Data

Reference Manual 00809-0100-4530, Rev BAJuly 2009C-17Rosemount 5300 SeriesNOTE!Single Rigid HTHP equipped with reference reflector is the only probe t

Page 186

Reference Manual00809-0100-4530, Rev BAJuly 2009Rosemount 5300 SeriesC-18Figure C-15. Minimum requirements.If a 5300 Series transmitter is ordered fro

Page 187

Reference Manual 00809-0100-4530, Rev BAJuly 2009C-19Rosemount 5300 SeriesTo calibrate Dynamic Vapor Compensation:1. Either choose Device Specific Con

Page 188

Reference Manual00809-0100-4530, Rev BAJuly 2009Rosemount 5300 SeriesC-20SIGNAL QUALITY METRICSSignal Quality Metrics indicates the surface signal int

Page 189

Reference Manual 00809-0100-4530, Rev BAJuly 2009C-21Rosemount 5300 SeriesFigure C-18. Check if Signal Quality Metrics is supported.3. If “Diagnostics

Page 190

Reference Manual 00809-0100-4530, Rev BAJuly 20092-13Rosemount 5300 SeriesFor measuring interface level, the transmitter uses the residual wave of the

Page 191

Reference Manual00809-0100-4530, Rev BAJuly 2009Rosemount 5300 SeriesC-22Signal Quality Metrics can be shown on the LCD panel. See “Operation” on page

Page 192

Reference Manual 00809-0100-4530, Rev BAJuly 2009D-1Rosemount 5300 SeriesAppendix D Remote MountingRemote Housing, New Units . . . . . . . . . . . .

Page 193

Reference Manual00809-0100-4530, Rev BAJuly 2009Rosemount 5300 SeriesD-2M6 screwFasten the housing support to the bracketFasten the housing support to

Page 194

Reference Manual 00809-0100-4530, Rev BAJuly 2009D-3Rosemount 5300 SeriesREMOTE CONNECTION, FIELD RETROFITTo upgrade a currently installed Rosemount 5

Page 195

Reference Manual00809-0100-4530, Rev BAJuly 2009Rosemount 5300 SeriesD-4REMOTE HOUSING CONFIGURATIONWhen using remote housing, the remote connection l

Page 196

Reference Manual 00809-0100-4530, Rev BAJuly 2009Rosemount 5300 Serieswww.rosemount.comAppendix E Performing Proof TestPerforming Proof Test . . . .

Page 197

Reference Manual00809-0100-4530, Rev BAJuly 2009Rosemount 5300 SeriesE-2Figure E-1. Range Values.5. Perform a two-point calibration check of the trans

Page 198

Reference Manual 00809-0100-4530, Rev BAJuly 2009E-3Rosemount 5300 SeriesROSEMOUNT RADAR MASTER (RRM)Prior to this test, inspect the echo curve to ens

Page 199

Reference Manual00809-0100-4530, Rev BAJuly 2009Rosemount 5300 SeriesE-45. Restore the Alarm mode to the original mode used in the loop. Verify that t

Page 200

Reference Manual 00809-0100-4530, Rev BAJuly 2009E-5Rosemount 5300 SeriesAMS SUITE Prior to this test, inspect the echo curve to ensure that no distur

Page 201

Reference Manual00809-0100-4530, Rev BAJuly 2009Rosemount 5300 Series2-14Figure 2-10. Maximum Upper Product thickness for the Flexible Twin Lead probe

Page 202

Reference Manual00809-0100-4530, Rev BAJuly 2009Rosemount 5300 SeriesE-64. Using loop test, enter the mA value representing the low alarm mode. Verify

Page 203

Reference Manual 00809-0100-4530, Rev BAJuly 2009Rosemount 5300 Serieswww.rosemount.comAppendix F Level Transducer BlockOverview . . . . . . . . . .

Page 204

Reference Manual00809-0100-4530, Rev BAJuly 2009Rosemount 5300 SeriesF-2Channel Definitions Each input has an assigned channel which can be linked to

Page 205

Reference Manual 00809-0100-4530, Rev BAJuly 2009F-3Rosemount 5300 SeriesBLOCK_ALM 8 The block alarm is used for all configuration, hardware, connecti

Page 206

Reference Manual00809-0100-4530, Rev BAJuly 2009Rosemount 5300 SeriesF-4TCL 37 This parameter is used for User Defined probes only. Please contact Eme

Page 207

Reference Manual 00809-0100-4530, Rev BAJuly 2009F-5Rosemount 5300 SeriesTable F-3. Probe TypeSTATS_TIMEOUTS 71 The total number of timed out A/D boa

Page 208

Reference Manual00809-0100-4530, Rev BAJuly 2009Rosemount 5300 SeriesF-6Table F-4. Device ModeTable F-5. EnvironmentTable F-6. PresentationTable F-

Page 209

Reference Manual 00809-0100-4530, Rev BAJuly 2009F-7Rosemount 5300 SeriesTable F-8. Product Dielectrical RangeTable F-9. Measurement Mode16 0x000100

Page 210

Reference Manual00809-0100-4530, Rev BAJuly 2009Rosemount 5300 SeriesF-8SUPPORTED UNITSUnit CodesTable F-10. LengthTable F-11. Level RateTable F-12.

Page 211

Reference Manual 00809-0100-4530, Rev BAJuly 2009F-9Rosemount 5300 SeriesDIAGNOSTICS DEVICE ERRORSIn addition to the BLOCK_ERR and XD_ERROR parameters

Page 212

Reference Manual 00809-0100-4530, Rev BAJuly 20092-15Rosemount 5300 SeriesINSTALLATION PROCEDUREFollow these steps for proper installation:Review Moun

Page 213

Reference Manual00809-0100-4530, Rev BAJuly 2009Rosemount 5300 SeriesF-10

Page 214

Reference Manual 00809-0100-4530, Rev BAJuly 2009G-1Rosemount 5300 SeriesAppendix G Register Transducer BlockOVERVIEW The Register Transducer Block al

Page 215

Reference Manual00809-0100-4530, Rev BAJuly 2009Rosemount 5300 SeriesG-2XD_ERROR 11 A transducer block alarm subcode.COLLECTION_DIRECTORY 12INP_SEARCH

Page 216

Reference Manual 00809-0100-4530, Rev BAJuly 2009G-3Rosemount 5300 SeriesDB_REG_2_FLOAT 49 If the register contains a float value, it should be displa

Page 217

Reference Manual00809-0100-4530, Rev BAJuly 2009Rosemount 5300 SeriesG-4

Page 218

Reference Manual 00809-0100-4530, Rev BAJuly 2009H-1Rosemount 5300 SeriesAppendix H Advanced Configuration Transducer BlockOVERVIEW The Advanced Confi

Page 219

Reference Manual00809-0100-4530, Rev BAJuly 2009Rosemount 5300 SeriesH-2AMPLITUDE_THRESHOLD_CURVE 13 ATC: filters out weak disturbance echoes and nois

Page 220

Reference Manual 00809-0100-4530, Rev BAJuly 2009H-3Rosemount 5300 SeriesVOL_VOLUME_OFFSET 46 Use this parameter to add a volume to each calculated v

Page 221

Reference Manual00809-0100-4530, Rev BAJuly 2009Rosemount 5300 SeriesH-4

Page 222

Reference Manual 00809-0100-4530, Rev BAJuly 2009I-1Rosemount 5300 SeriesAppendix I Resource Transducer BlockOverview . . . . . . . . . . . . . . . .

Page 223

Reference Manual 00809-0100-4530, Rev BAJuly 2009Rosemount 5300 Serieswww.rosemount.comRosemount 5300 Series Guided Wave Radar Level and Interface Tra

Page 224

Reference Manual00809-0100-4530, Rev BAJuly 2009Rosemount 5300 Series2-16

Page 225

Reference Manual00809-0100-4530, Rev BAJuly 2009Rosemount 5300 SeriesI-2CYCLE_TYPE 19 Identifies the block execution methods available for this resour

Page 226

Reference Manual 00809-0100-4530, Rev BAJuly 2009I-3Rosemount 5300 SeriesMAINT_ALM 78 Alarm indicating the device needs maintenance soon. If the condi

Page 227

Reference Manual00809-0100-4530, Rev BAJuly 2009Rosemount 5300 SeriesI-4SAVE_CONFIG_NOW 61 Allows the user to optionally save all non-volatile informa

Page 228

Reference Manual 00809-0100-4530, Rev BAJuly 2009I-5Rosemount 5300 SeriesPlantWeb™ Alerts The Resource Block will act as a coordinator for PlantWeb al

Page 229

Reference Manual00809-0100-4530, Rev BAJuly 2009Rosemount 5300 SeriesI-6MAINT_ENABLEDThe MAINT_ENABLED parameter contains a list of conditions indicat

Page 230

Reference Manual 00809-0100-4530, Rev BAJuly 2009I-7Rosemount 5300 SeriesADVISE_ACTIVEThe ADVISE_ACTIVE parameter displays which of the advisories is

Page 231

Reference Manual00809-0100-4530, Rev BAJuly 2009Rosemount 5300 SeriesI-8Table I-1. RB.RECOMMENDED_ACTION Alarm TypeFailed/Maint/AdviseActive EventRec

Page 232

Reference Manual 00809-0100-4530, Rev BAJuly 2009J-1Rosemount 5300 SeriesAppendix J Analog-Input BlockSimulation . . . . . . . . . . . . . . . . . .

Page 233

Reference Manual00809-0100-4530, Rev BAJuly 2009Rosemount 5300 SeriesJ-2Table J-1. Definitions of Analog Input Function Block System ParametersParame

Page 234

Reference Manual 00809-0100-4530, Rev BAJuly 2009J-3Rosemount 5300 SeriesSIMULATION To support testing, you can either change the mode of the block to

Page 235

Reference Manual 00809-0100-4530, Rev BAJuly 2009Rosemount 5300 Serieswww.rosemount.comSection 3 Mechanical InstallationSafety messages . . . . . . .

Page 236

Reference Manual00809-0100-4530, Rev BAJuly 2009Rosemount 5300 SeriesJ-4Figure J-2. Analog Input Function Block SchematicFigure J-3. Analog Input Func

Page 237

Reference Manual 00809-0100-4530, Rev BAJuly 2009J-5Rosemount 5300 SeriesSIGNAL CONVERSION You can set the signal conversion type with the Linearizati

Page 238

Reference Manual00809-0100-4530, Rev BAJuly 2009Rosemount 5300 SeriesJ-6BLOCK ERRORS Table J-2 lists conditions reported in the BLOCK_ERR parameter. T

Page 239

Reference Manual 00809-0100-4530, Rev BAJuly 2009J-7Rosemount 5300 SeriesALARM DETECTION A block alarm will be generated whenever the BLOCK_ERR has an

Page 240

Reference Manual00809-0100-4530, Rev BAJuly 2009Rosemount 5300 SeriesJ-8Status Handling Normally, the status of the PV reflects the status of the meas

Page 241

Reference Manual 00809-0100-4530, Rev BAJuly 2009J-9Rosemount 5300 SeriesCONFIGURE THE AI BLOCKA minimum of four parameters are required to configure

Page 242

Reference Manual00809-0100-4530, Rev BAJuly 2009Rosemount 5300 SeriesJ-10Indirect Square RootSelect indirect square root when the desired output is an

Page 243

Reference Manual 00809-0100-4530, Rev BAJuly 2009J-11Rosemount 5300 SeriesTable J-6. TemperatureTable J-7. Signal StrengthTable J-8. VolumeDisplay

Page 244

Reference Manual00809-0100-4530, Rev BAJuly 2009Rosemount 5300 SeriesJ-12

Page 245

Reference Manual 00809-0100-4530, Rev BAJuly 2009Rosemount 5300 Serieswww.rosemount.comIndexNumerics375 Field Communicator . . . . 5-11751 Field Sig

Page 246

Reference Manual00809-0100-4530, Rev BAJuly 2009Rosemount 5300 Series3-2Any substitution of non-authorized parts or repair, other than exchanging the

Page 247

Reference Manual00809-0100-4530, Rev BAJuly 2009Rosemount 5300 SeriesIndex-2IIndirect . . . . 5-39, 5-40, J-9, J-10Indirect Signal Conversion . . .

Page 248

Reference Manual 00809-0100-4530, Rev BAJuly 2009Index-3Rosemount 5300 SeriesTri-loop . . . . . . . . . . . . . . . . . . . 2-7Troubleshooting . . .

Page 249

Reference Manual00809-0100-4530, Rev BAJuly 2009Rosemount 5300 SeriesIndex-4

Page 251

Reference Manual 00809-0100-4530, Rev BAJuly 2009Rosemount 5300 Series00809-0100-4530 Rev BA, 06/09Standard Terms and Conditions of Sale can be found

Page 252

Reference Manual 00809-0100-4530, Rev BAJuly 20093-3Rosemount 5300 SeriesMOUNTING CONSIDERATIONSBefore installing the Rosemount 5300 Series Radar Tran

Page 253

Reference Manual00809-0100-4530, Rev BAJuly 2009Rosemount 5300 Series3-4The transmitter can be mounted in nozzles by using an appropriate flange. The

Page 254

Reference Manual 00809-0100-4530, Rev BAJuly 20093-5Rosemount 5300 SeriesA long stud - 10 in. (250 mm) - is recommended for single flexible probes in

Page 255

Reference Manual00809-0100-4530, Rev BAJuly 2009Rosemount 5300 Series3-6Installation in Concrete SilosConsiderations for Solid ApplicationsThe flexibl

Page 256

Reference Manual 00809-0100-4530, Rev BAJuly 20093-7Rosemount 5300 SeriesTable 3-2. Pulling force on probe installed in tanks with different products

Page 257

Reference Manual00809-0100-4530, Rev BAJuly 2009Rosemount 5300 Series3-8Figure 3-5. Mounting Single Probe in Chamber/Still PipeInlet pipe diameter N&l

Page 258

Reference Manual 00809-0100-4530, Rev BAJuly 20093-9Rosemount 5300 SeriesA short weight for the single flexible 0.16 in. (4 mm) SST probe can be used

Page 260

Reference Manual00809-0100-4530, Rev BAJuly 2009Rosemount 5300 Series3-10NOTE!The formulas are not valid when using Dynamic Vapor Compensation probes.

Page 261

Reference Manual 00809-0100-4530, Rev BAJuly 20093-11Rosemount 5300 SeriesFree Space For easy access to the transmitter, make sure it is mounted with

Page 262

Reference Manual00809-0100-4530, Rev BAJuly 2009Rosemount 5300 Series3-12Recommended Mounting Position for LiquidsTank conditions are recommended to b

Page 263

Reference Manual 00809-0100-4530, Rev BAJuly 20093-13Rosemount 5300 SeriesRecommended Mounting for SolidsConsider the following guidelines when mounti

Page 264

Reference Manual00809-0100-4530, Rev BAJuly 2009Rosemount 5300 Series3-14Insulated Tanks When the Rosemount 5300 is installed in high temperature appl

Page 265

Reference Manual 00809-0100-4530, Rev BAJuly 20093-15Rosemount 5300 SeriesMOUNTING Mount the transmitter with flange on a nozzle on top of the tank. T

Page 266

Reference Manual00809-0100-4530, Rev BAJuly 2009Rosemount 5300 Series3-16Figure 3-11. Tank connection with loose flange (“plate design”).Threaded Conn

Page 267

Reference Manual 00809-0100-4530, Rev BAJuly 20093-17Rosemount 5300 SeriesTri-Clamp ConnectionFigure 3-13. Tri-Clamp tank connection.Tri-ClampProbeTra

Page 268

Reference Manual00809-0100-4530, Rev BAJuly 2009Rosemount 5300 Series3-18Bracket MountingMount the bracket to the pole1. Put the two U-bolts through t

Page 269

Reference Manual 00809-0100-4530, Rev BAJuly 20093-19Rosemount 5300 SeriesShortening the Probe NOTE!HTHP Coaxial and PTFE probes must not be shortene

Page 270

Reference Manual 00809-0100-4530, Rev BAJuly 2009Rosemount 5300 Serieswww.rosemount.comTable of ContentsSECTION 1IntroductionSafety Messages . . . . .

Page 271 - Appendix D Remote Mounting

Reference Manual00809-0100-4530, Rev BAJuly 2009Rosemount 5300 Series3-20Rigid Twin LeadThe spacers are put closer together at the probe end. The maxi

Page 272

Reference Manual 00809-0100-4530, Rev BAJuly 20093-21Rosemount 5300 SeriesCoaxialTo cut a coaxial probe:NOTE!The HTHP coaxial probe must not be cut in

Page 273

Reference Manual00809-0100-4530, Rev BAJuly 2009Rosemount 5300 Series3-22Anchoring In turbulent tanks, it may be necessary to fix the probe. Depending

Page 274

Reference Manual 00809-0100-4530, Rev BAJuly 20093-23Rosemount 5300 SeriesCoaxial probe.The Coaxial probe can be guided by a tube welded on the tank b

Page 275

Reference Manual00809-0100-4530, Rev BAJuly 2009Rosemount 5300 Series3-24Solid ApplicationsPull the probe rope through a suitable anchoring point, e.g

Page 276

Reference Manual 00809-0100-4530, Rev BAJuly 20093-25Rosemount 5300 SeriesMounting a Centering Disc for Pipe InstallationsTo prevent the probe from co

Page 277

Reference Manual00809-0100-4530, Rev BAJuly 2009Rosemount 5300 Series3-26Mounting a Centering Disc on Rigid Single ProbesThe mounting of a centering d

Page 278

Reference Manual 00809-0100-4530, Rev BAJuly 20093-27Rosemount 5300 SeriesRigid Single Lead probe (8 mm)NOTE!The washer should not be used if the disc

Page 279

Reference Manual00809-0100-4530, Rev BAJuly 2009Rosemount 5300 Series3-28

Page 280

Reference Manual 00809-0100-4530, Rev BAJuly 2009Rosemount 5300 Serieswww.rosemount.comSection 4 Electrical InstallationSafety messages . . . . . . .

Page 281

Reference Manual00809-0100-4530, Rev BAJuly 2009Rosemount 5300 SeriesTOC-2SECTION 4Electrical InstallationSafety messages . . . . . . . . . . . . . .

Page 282

Reference Manual00809-0100-4530, Rev BAJuly 2009Rosemount 5300 Series4-2High voltage that may be present on leads could cause electrical shock:Avoid c

Page 283

Reference Manual 00809-0100-4530, Rev BAJuly 20094-3Rosemount 5300 SeriesCABLE/CONDUIT ENTRIESThe electronics housing has two entries for ½ - 14 NPT.

Page 284

Reference Manual00809-0100-4530, Rev BAJuly 2009Rosemount 5300 Series4-4HARTPower Requirements Terminals in the transmitter housing provide connection

Page 285

Reference Manual 00809-0100-4530, Rev BAJuly 20094-5Rosemount 5300 SeriesConnecting the TransmitterTo connect the Rosemount 5300 Series transmitter:1.

Page 286

Reference Manual00809-0100-4530, Rev BAJuly 2009Rosemount 5300 Series4-6Non-Intrinsically Safe Output With non-intrinsically safe power supply in non-

Page 287

Reference Manual 00809-0100-4530, Rev BAJuly 20094-7Rosemount 5300 SeriesIntrinsically Safe Output For intrinsically safe installations wire the trans

Page 288

Reference Manual00809-0100-4530, Rev BAJuly 2009Rosemount 5300 Series4-8FOUNDATION FIELDBUSPower Requirements Terminals in the transmitter housing pro

Page 289

Reference Manual 00809-0100-4530, Rev BAJuly 20094-9Rosemount 5300 SeriesFigure 4-7. Terminal compartment and external ground screw.Cable entries.Inte

Page 290

Reference Manual00809-0100-4530, Rev BAJuly 2009Rosemount 5300 Series4-10Connecting Fieldbus DevicesFigure 4-8. Rosemount 5300 Radar Transmitter field

Page 291

Reference Manual 00809-0100-4530, Rev BAJuly 20094-11Rosemount 5300 SeriesNon-Intrinsically Safe Output With non-intrinsically safe power supply in No

Page 292

Reference Manual 00809-0100-4530, Rev BAJuly 2009TOC-3Rosemount 5300 SeriesDevice Specific Configuration. . . . . . . . . . . . . . . . . . . . . . .

Page 293

Reference Manual00809-0100-4530, Rev BAJuly 2009Rosemount 5300 Series4-12Intrinsically Safe Output When your power supply is intrinsically safe, wire

Page 294

Reference Manual 00809-0100-4530, Rev BAJuly 20094-13Rosemount 5300 SeriesOPTIONAL DEVICESTri-Loop HART to analog converterThe Rosemount 5300 transmit

Page 295 - Transducer Block

Reference Manual00809-0100-4530, Rev BAJuly 2009Rosemount 5300 Series4-14751 Field Signal IndicatorFigure 4-12. Wiring diagram for a Rosemount 5300 tr

Page 296

Reference Manual 00809-0100-4530, Rev BAJuly 2009Rosemount 5300 Serieswww.rosemount.comSection 5 ConfigurationSafety messages . . . . . . . . . . . .

Page 297

Reference Manual00809-0100-4530, Rev BAJuly 2009Rosemount 5300 Series5-2OVERVIEW The configuration of a Rosemount 5300 transmitter is normally a simpl

Page 298

Reference Manual 00809-0100-4530, Rev BAJuly 20095-3Rosemount 5300 SeriesRRM is a user-friendly, Windows® based software package including waveform pl

Page 299

Reference Manual00809-0100-4530, Rev BAJuly 2009Rosemount 5300 Series5-4BASIC CONFIGURATION PARAMETERSThis section describes basic configuration param

Page 300

Reference Manual 00809-0100-4530, Rev BAJuly 20095-5Rosemount 5300 SeriesTank HeightThe Tank Height is defined as the distance from the Upper Referenc

Page 301

Reference Manual00809-0100-4530, Rev BAJuly 2009Rosemount 5300 Series5-6Hold Off/Upper Null ZoneThis parameter should only be changed if there are mea

Page 302

Reference Manual 00809-0100-4530, Rev BAJuly 20095-7Rosemount 5300 SeriesNormally, this parameter does not need to be changed even if the actual diele

Page 303

Reference Manual00809-0100-4530, Rev BAJuly 2009Rosemount 5300 SeriesTOC-4Changing a Probe . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Page 304

Reference Manual00809-0100-4530, Rev BAJuly 2009Rosemount 5300 Series5-8Standard Tank ShapesFigure 5-4. Standard tank shapesVertical CylinderVertical

Page 305

Reference Manual 00809-0100-4530, Rev BAJuly 20095-9Rosemount 5300 SeriesAnalog Output (HART) The Output Source (Primary Value), Range Values and Alar

Page 306

Reference Manual00809-0100-4530, Rev BAJuly 2009Rosemount 5300 Series5-10Alarm ModeThe Alarm mode specifies the analog output state when there is a fa

Page 307 - Appendix J Analog-Input Block

Reference Manual 00809-0100-4530, Rev BAJuly 20095-11Rosemount 5300 SeriesBASIC CONFIGURATION USING A 375 FIELD COMMUNICATORThis section describes how

Page 308

Reference Manual00809-0100-4530, Rev BAJuly 2009Rosemount 5300 Series5-12Figure 5-7. HART Communicator Menu Tree corresponding to Device Revision 3.Pr

Page 309

Reference Manual 00809-0100-4530, Rev BAJuly 20095-13Rosemount 5300 SeriesBASIC CONFIGURATION USING ROSEMOUNT RADAR MASTERThe Rosemount Radar Master (

Page 310

Reference Manual00809-0100-4530, Rev BAJuly 2009Rosemount 5300 Series5-14Installing the RRM software for HART communicationTo install the Rosemount Ra

Page 311

Reference Manual 00809-0100-4530, Rev BAJuly 20095-15Rosemount 5300 SeriesSpecifying the COM Port If communication is not established, open the Commun

Page 312

Reference Manual00809-0100-4530, Rev BAJuly 2009Rosemount 5300 Series5-16Installing the RRM Software for FOUNDATION FieldbusTo install the Rosemount R

Page 313

Reference Manual 00809-0100-4530, Rev BAJuly 20095-17Rosemount 5300 Series2. Start Rosemount Radar Master (RRM): from the Start menu click Programs>

Page 314

Reference Manual 00809-0100-4530, Rev BAJuly 2009TOC-5Rosemount 5300 SeriesAPPENDIX BProduct CertificationsSafety messages . . . . . . . . . . . . . .

Page 315

Reference Manual00809-0100-4530, Rev BAJuly 2009Rosemount 5300 Series5-18Using the Setup FunctionsUse the Setup function if you are already familiar w

Page 316

Reference Manual 00809-0100-4530, Rev BAJuly 20095-19Rosemount 5300 SeriesGuided Setup The following description shows how to use the RRM Guided Setup

Page 317

Reference Manual00809-0100-4530, Rev BAJuly 2009Rosemount 5300 Series5-20Device Properties3. Check the device propertiesThe first window in the config

Page 318

Reference Manual 00809-0100-4530, Rev BAJuly 20095-21Rosemount 5300 SeriesProbe5. Probe settingsHART command: [2, 1, 2].FOUNDATION Fieldbus parameters

Page 319

Reference Manual00809-0100-4530, Rev BAJuly 2009Rosemount 5300 Series5-22Geometry6. GeometryHART command: [2, 1, 3].FOUNDATION Fieldbus parameter:TRAN

Page 320

Reference Manual 00809-0100-4530, Rev BAJuly 20095-23Rosemount 5300 SeriesTank Environment7. Specify Tank EnvironmentHART command: [2, 1, 4].FOUNDATIO

Page 321

Reference Manual00809-0100-4530, Rev BAJuly 2009Rosemount 5300 Series5-24Rosemount Radar Master (RRM) includes tools to estimate the dielectric consta

Page 322

Reference Manual 00809-0100-4530, Rev BAJuly 20095-25Rosemount 5300 SeriesVolume8. Choose Volume Calculation MethodHART command: [2, 1, 5].FOUNDATION

Page 323

Reference Manual00809-0100-4530, Rev BAJuly 2009Rosemount 5300 Series5-26Analog Output (HART)9. Configure the Analog OutputHART command: [2,1, 6].Anal

Page 324

Reference Manual 00809-0100-4530, Rev BAJuly 20095-27Rosemount 5300 SeriesDevice Specific Configuration11. Click the Device specific setup button12. T

Commentaires sur ces manuels

Pas de commentaire