Reference Manual
00809-0100-4530, Rev BA
July 2009
Rosemount 5300 Series
5-42
Application Example 1 Radar Level Transmitter, Level Value
A level transmitter is measuring the level in a 33 ft. (10 m) high tank.
Figure 5-12. Situation Diagram
Solution
Table 5-9 lists the appropriate configuration settings, and Figure 5-13
illustrates the correct function block configuration.
Table 5-9. Analog Input
Function Block Configuration for
a typical Level Transmitter
Figure 5-13. Analog Input
Function Block Diagram for a
typical Level Transmitter
33 ft
(10 m)
100%
0%
Parameter Configured Values
L_TYPE Direct
XD_SCALE Not Used
OUT_SCALE Not Used
CHANNEL CH1: Level
Level Measurement
To Another
Function Block
OUT_D
OUT
AI Function Block