Emerson Process Management ROSEMOUNT 5300 Manuel d'utilisateur Page 65

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 324
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 64
Reference Manual
00809-0100-4530, Rev BA
July 2009
4-7
Rosemount 5300 Series
Intrinsically Safe Output For intrinsically safe installations wire the transmitter as shown in Figure 4-6.
NOTE!
Make sure the instruments in the loop are installed in accordance with
intrinsically safe field wiring practices and System Control Drawings when
applicable.
Figure 4-6. Wiring diagram for
intrinsically safe installations
(HART).
For HART communication, a minimum load resistance of 250 within the
loop is required. For maximum load resistance see Figure 4-3.
The power supply voltage ranges from 16 Vdc to 30 Vdc.
IS parameters
(1)
Ui=30 V.
Ii=130 mA.
Pi=1 W.
Ci=7.26 nF.
Li=0.
Load Resistance
Power
Supply
375 Field
Communicator
Rosemount 5300 Series
Radar Transmitter
HART modem
RRM
AMS Suite
250
Approved IS Barrier
(1) See Section B: Product Certifications for more information.
Vue de la page 64
1 2 ... 60 61 62 63 64 65 66 67 68 69 70 ... 323 324

Commentaires sur ces manuels

Pas de commentaire